TESTING NEW INSTALLATIONS TO IGEM/UP/1A

A new installation is deemed to have failed if there is a perceivable drop on the gauge, the test recognises that different types of gauge read to different accuracies.

Installation Volume Tightness test duration  for water, and 0.5 mbar accuracy electronic gauges. Tightness test duration for 0.1mbar accuracy electronic gauges.
Volume in metres³ Time in Minutes Time in minutes
Up to 0.06 2 2
>0.06 up to 0.09 3 2
>0.09 up to 0.12 4 2
>0.12 up to 0.15 5 2
>0.15 up to 0.18 6 2
>0.18 up to 0.21 7 2
>0.21 up to 0.24 8 2
>0.24 up yo 0.27 9 2
>0.27 up to 0.3 10 2
>0.3 up to 0.33 11 3
>0.33 up to 0.36 12 3
>0.36 up to 0.39 13 3
>0.39 up to 0.42 14 3
>0.42 up to 0.45 15 3
>0.45 up to 0.48 16 4
>0.48 up to 0.51 17 4
>0.51 up to 0.54 18 4
>0.54 up to 0.57 19 4
>0.57 up to 0.6 20 4
>0.6 up to 0.63 21 5
>0.63 up to 0.66 22 5
>0.66 up to 0.69 23 5
>0.69 up to 0.72 24 5
>0.72 up to 0.75 25 5
>0.75 up to 0.78 26 6
>0.78 up to 0.81 27 6
>0.81 up to 0.84 28 6
>0.84 up to 0.87 29 6
>0.87 up to 0.9 30 6
>0.9 up to 0.93   7
>0.93 up to 0.96   7
>0.96 up to 1   7